发布时间 : 星期五 文章505E操作说明书(简明本)更新完毕开始阅读
21212128 广州广重企业集团有限公司 505E
控制器操
作说明书
(使用1#执行机构故障停机)
Act 1 (HP) Dither _________________________mA (1#执行机构颤震)
Act 1 Cal Min ____________________________mA (执行机构1#刻度下限)
Act 1 Cal Max ____________________________mA (执行机构1#刻度上限)
Act #2 (LP) is 4-20mA? _____ YES _____NO _____ (2#执行机构为4——20mA?)
Invert Driver Output ? ______ YES _____NO _____ (驱动输出反向?)
Use Act 2 Flt Shutdown _____ YES _____NO _____ (使用2#执行机构故障停机)
Act 2 (LP) Dither _________________________mA (2#执行机构颤震)
Act 2 Cal Min ____________________________mA (2#执行机构刻度值下限)
Act 2 Cal Max ____________________________mA (2#执行机构刻度值上限)
ANALOG INPUTS(模拟输入)
nalog Input # 1 Function _________ Extr/Admission (1#模拟输入功能)
Input 1 4mA Value ______________________Units (1#输入4mA值)
Input 1 20mAValue _________________ ____ Units (1#输入20mA值)
nalog Input # 2 Function ______________________ (2#模拟输入功能)
Input 2 4mA Value ______________________Units (2#输入4mA值)
Input 2 20mA Value _____________________Units (2#输入20m A值)
Analog Input # 3 Function ____________________ (3#模拟输入功能)
Input 3 4mA Value ______________________Units (3#输入4mA值)
Input 3 20mA Value _____________________Units (3#输入20m A值)
Analog Input # 4 Function ____________________ (4#模拟输入功能)
Input 4 4mA Value ______________________Units (4#输入4mA值)
Input 4 20mA Value _____________________Units (4#输入20m A值)
21
22222228 广州广重企业集团有限公司 505E
控制器操
作说明书
Analog Input # 5 Function ____________________ (5#模拟输入功能)
Input 5 4mA Value _____________________ Units (5#输入4mA值)
Input 5 20mA Value _____________________Units (5#输入20m A值)
Analog Input # 6 Function ____________________ (6#模拟输入功能)
Input 6 4mA Value ______________________Units (6#输入4mA值)
Input 6 20mA Value _____________________Units (6#输入20m A值)
CONTACT INPUTS(触点输入)
Contact Input 1 Function ______________________ (1#触点输入功能)
Contact Input 2 Function ______________________ (2#触点输入功能)
Contact Input 3 Function ______________________ (3#触点输入功能)
Contact Input 4 Function ______________________ (4#触点输入功能)
Contact Input 5 Function ______________________ (5#触点输入功能)
Contact Input 6 Function ______________________ (6#触点输入功能)
Contact Input 7 Function ______________________ (7#触点输入功能)
Contact Input 8 Function ______________________ (8#触点输入功能)
Contact Input 9 Function ______________________ (9#触点输入功能)
Contact Input 10 Fctn ________________________ (10#触点输入功能)
ontact Input 11 Fctn _________________________ (11#触点输入功能)
Contact Input 12 Fctn ________________________ (12#触点输入功能)
FUNCTION KEYS(功能键)
F3 Key Performs ____________________________ (F3键执行)
Blink when not Active? ____ YES _____NO _____ (未激活时闪烁?)
F4 Key Performs ____________________________ (F4键执行)
22
23232328 广州广重企业集团有限公司 505E
控制器操
作说明书
Blink when not Active? ____ YES _____NO _____ (未激活时闪烁?)
AUXILIARY CONTROL(辅助控制)
Use Auxiliary Control ? ____ YES _____ NO _____ (使用辅助控制?)
Lost Aux Input Shutdown? __ YES_ ____ NO _____ (失去辅助时停机?)
Use KW Input ? ___________ YES _____ NO _____ (使用KW输入?)
Invert Aux ? _____________ YES _____ NO _____ (辅助输入反向?)
Min Aux Setpt _________________________Units (辅助给定值下限)
Max Aux Setpt _________________________Units (辅助给定值上限)
Aux Setpt Rate units/sec _____________Units / SEC (辅助给定值速率)
Use Aux Enable? __________ YES _____ NO _____ (使用辅助投入?)
Setpt Initial Value _______________________Units (初始给定值)
Aux Droop _______________________________ % (辅助不等率)
Aux PID Prop Gain ________________________ % (复制PID比例增益)
Aux PID Integral Gain _____________________rps (辅助PID积分增益)
Aux Derivative Ratio ______________________ % (辅助PID微分率)
Tiebrkr Open Aux Disable ___ YES ____NO _____ (电网断路器断开时退出辅助控制)
Genbrkr Open Aux Disable ___ YES ____NO _____ (发电机断路器断开时退出辅助控制)
Use Remote Aux Setting_____ YES _____ NO ____ (采用远程辅助给定值)
Remote Aux Max Rate _____________ Units / SEC (远程辅助最大速率)
Aux Units of Measure ________________________ (辅助控制的测量单位)
CASCADE CONTROL(串级控制)
Use Cascade Control? ______ YES _____NO _____ (使用串级控制?)
Invert Cascade ? __________ YES _____NO _____
23
24242428 广州广重企业集团有限公司 505E
控制器操
作说明书
(反向串级控制?)
Min Cascade Setpt _____________________ Units (串级给定值下限)
Max Cascade Setpt ______________________ Units (串级给定值上限)
Casc Setpt Rate (/sec) _______________ Units/SEC (串级给定值速率)
Use Setpoint Tracking ? _____ YES _____NO _____ (使用给定值跟踪功能?)
Setpt Initial Value _______________________ Units (初始给定值)
Speed Setpt Lower Limit __________________RPM (转速给定值下限)
Speed Setpt Upper Limit __________________RPM (转速给定值上限)
Max Speed Rate(RPM/sec) ____________ RPM/Sec (最大转速速率)
Cascade Droop ____________________________ % (串级控制不等率)
Casc PID Prop Gain ________________________ % (串级PID比例增益)
Casc PID Integral Gain ____________________ rps (串级PID积分增益)
Casc Derivative Ratio ______________________ % (串级微分率)
Use Remote Casc Setting ____ YES _____NO _____ (采用远程串级给定值)
Remote Casc Max Rate ______________ Units/SEC (远程串级最大速率)
Casc Units of Measure ________________________ (串级控制的测量单位) READOUTS(读数输出)
Analog Readout 1 Is _________________________ (1#模拟读书输出为)
Readout 1 4mA Value ___________________ Units (1#读数输出 4mA值)
Readout 1 20mA Value __________________ Units (1#读数输出 20mA值)
Analog Readout 2 Is _________________________ (2#模拟读书输出为)
Readout 2 4mA Value ___________________ Units (2#读数输出 4mA值)
eadout 2 20mA Value ____________________ Units (2#读数输出 20mA值)
24